Huawei NetCol8000-C User Manual page 192

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C:
Table of Contents

Advertisement

NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Alar
Alarm
m ID
Name
power 24 V
overvoltage
a168
Auxiliary
power 24 V
undervoltag
e
a172
SPD
3-phase
detect brd
comm
interrupt
a174
SPD failed
a179
Humid
pump
abnormal
a180
Humidifier
wet film
replace
due-in alarm
a181
Humidifier
pump
exceed
runtime
alarm
a182
Water
Supply
Issue 06 (2020-01-13)
Alarm
Impact
Severi
ty
triggered.
Major
An alarm is
triggered.
Major
An alarm is
triggered.
Major
An alarm is
triggered.
Major
An alarm is
triggered,
and the
humidifier is
shut down.
Warnin
An alarm is
g
triggered.
Warnin
An alarm is
g
triggered.
Major
An alarm is
triggered.
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
faulty.
The auxiliary power supply is
faulty.
1. The communications cable
is loose or damaged.
2. The SPD three-phase
detection board is faulty.
3. The communications port
of the main control board is
faulty.
The SPD three-phase test board
is faulty.
1. The water pump inlet is
blocked.
2. Cables to the humidifier
pump are loose or damaged.
3. The humidifier pump is
faulty.
4. The water pump races due
to a liquid level detection
fault.
5. The humidifier pump is
blocked.
The accumulated runtime of
the wet film of the humidifier
exceeds the alarm threshold.
The accumulated runtime of
the water pump exceeds the
alarm threshold.
1. The water supply is
insufficient.
2. The humidifier float has
6 System Operation and Maintenance
Solution
power supply module.
Replace the auxiliary
power supply module.
1. Check the
communications
cable.
2. Replace the SPD
three-phase detection
board.
3. Maintain or replace
the main control
board.
Replace the SPD
three-phase test board.
1. Clear the blockage
from the water pump
inlet.
2. Verify that the
humidifier pump cable
is properly connected.
3. Replace the pump if it
is faulty.
4. Rectify the liquid
level detection fault.
5. Replace the water
pump.
NOTE
After the fault is rectified,
click Clear on the alarm
page to manually clear the
alarm.
Maintain or replace the
wet film of the humidifier
and clear the accumulated
runtime.
Maintain or replace the
water pump and clear the
accumulated runtime.
1. Verify that water
supply to the
humidifier is normal.
184