Huawei NetCol8000-C User Manual page 31

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C:
Table of Contents

Advertisement

NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Pipe Dimensions
The following table lists the reserved pipe dimensions of a NetCol8000-C.
Table 2-3 Pipe dimensions
Item
Water outlet pipe
Water inlet pipe
Humidifier water inlet pipe
Drainpipe
Installation Requirements
Table 2-4 Installation requirements
Item
Door
Floor
Pipe routing
Maintenance distance
Power distribution requirements
Operating Specifications
Table 2-5 Operating specifications
Item
Operating temperature
Operating humidity
Temperature of inlet chilled water (or
glycol)
Storage temperature
Issue 06 (2020-01-13)
a
Copyright © Huawei Technologies Co., Ltd.
Specifications
G 2 inch port with inner threads
G 2 inch port with inner threads
G 1/2 inch port with inner threads
BSPP 3/4 inch port with inner threads
Specifications
Width ≥ 1.3 m; height ≥ 2.3 m
Floor bearing capacity ≥ 400 kg/m
Left and bottom pipe routing, and left pipe
routing
Front maintenance distance ≥ 900 mm
Leakage circuit breakers are not
recommended for the active power supply
route. If a leakage circuit breaker is required
by the customer or local regulations, select
the residual current circuit breaker (RCCB)
that is insensitive to single-phase DC
pulsation and transient impulse current.
Specifications
4–45° C
20%–80% RH
4–20° C
–40° C to +70° C
2 Product Overview
2
23

Advertisement

Table of Contents
loading

Table of Contents