3.5.2.2 Downflow

3.5.2.2.1 Bottom Pipe Routing

Context
Tools: 75# open-end wrench, 36# open-end wrench, 18# pipe wrench, sealant (used for
pasting thermal insulation foam), screw thread sealant
Procedure
Step 1 Remove the baffle plate at the bottom of the cabinet, and knock off the U-shaped hole in the
baffle plate, as shown by (1) in
Step 2 To avoid deforming the pipe, use a 75# open-end wrench to fix the pipe nut, use a 36#
open-end wrench to fix the plug, and then remove the plug, as shown by (2) in
Step 3 Apply thread sealant evenly on the joints of external screw threads, and install the pipes from
inside out, as shown by (3) in
Step 4 Use a 75# open-end wrench and 18# pipe wrench to fix the pipe, as shown by (4) in
3-40.
Step 5 Install the pipe baffle plate at the bottom of the cabinet, and wrap the pipe with thermal
insulation foam, as shown by (5) in
Issue 06 (2020-01-13)
Connect pipes and then wrap thermal insulation foam around the whole pipeline.
Based on the hardening property of yellow adhesive, inject water and preserve the
pressureat least 8 hours after an adapter is connected.