NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Alar
Alarm
m ID
Name
a029
Power BC
overvoltage
a030
Power CA
overvoltage
a031
Power AB
undervoltag
e
a032
Power BC
undervoltag
e
a033
Power CA
undervoltag
e
a034
Power
overfreq
Issue 06 (2020-01-13)
Alarm
Impact
Severi
ty
system is
shut down.
Major
An alarm is
triggered,
and the
system is
shut down.
Major
An alarm is
triggered,
and the
system is
shut down.
Major
An alarm is
triggered,
and the
system is
shut down.
Major
An alarm is
triggered,
and the
system is
shut down.
Major
An alarm is
triggered,
and the
system is
shut down.
Major
An alarm is
triggered,
and the
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
2. The SPD three-phase
detection board is faulty.
1. The power supply voltage
exceeds the upper
threshold.
2. The SPD three-phase
detection board is faulty.
1. The power supply voltage
exceeds the upper
threshold.
2. The SPD three-phase
detection board is faulty.
1. The power supply voltage is
below the lower threshold.
2. The cables to the SPD
three-phase detection board
are loose or damaged.
3. The SPD three-phase
detection board is faulty.
1. The power supply voltage is
below the lower threshold.
2. The cables to the SPD
three-phase detection board
are loose or damaged.
3. The SPD three-phase
detection board is faulty.
1. The power supply voltage is
below the lower threshold.
2. The cables to the SPD
three-phase detection board
are loose or damaged.
3. The SPD three-phase
detection board is faulty.
1. The power supply
frequency exceeds the
upper threshold.
6 System Operation and Maintenance
Solution
range.
2. Replace the SPD
three-phase detection
board.
1. Check the power
supply voltage, and
ensure that the voltage
is within the operating
range.
2. Replace the SPD
three-phase detection
board.
1. Check the power
supply voltage, and
ensure that the voltage
is within the operating
range.
2. Replace the SPD
three-phase detection
board.
1. Check the power
supply voltage.
2. Check the cables to
the SPD three-phase
detection board.
3. Replace the SPD
three-phase detection
board.
1. Check the power
supply voltage.
2. Check the cables to
the SPD three-phase
detection board.
3. Replace the SPD
three-phase detection
board.
1. Check the power
supply voltage.
2. Check the cables to
the SPD three-phase
detection board.
3. Replace the SPD
three-phase detection
board.
1. Check the power
supply frequency, and
ensure that it is within
175