Figure 3-7 Pipe support (unit: mm)

3.1.3.5 Cables

When connecting cables, fit them with protective hoses.
Table 3-5 Description about the cables matching the C16A switch
Application
Scenario
Indoor unit
Issue 06 (2020-01-13)
The height of a U-shaped pipe clamp equals the diameter of the pipe with thermal insulation foam
minus 5 mm. The pipe supports are to be purchased.
Stainless steel 304 is recommended for pipe supports and pipe clamps.
Install a support every 2500 mm in the straight sections of pipes, and 1000 mm away from each
bending point in the turning section.
The site ground resistance must be less than 0.1 ohm.
The cable flame spread rating must be at least VB.
Select power cables with appropriate diameters based on the maximum working currents.
Name
Power cable
(optional)
Copyright © Huawei Technologies Co., Ltd.
Technical Requirements
Electrical power cable, 600 V/1000 V,
2
ZA-RVV, 5 x 2.5 mm
, black (five
core wires: red, yellow, green, blue,
black), 27 A, outdoor cable, CE
3 Installation Guide
Remarks
The length is
determined
based on site
survey.
The neutral wire
is not required
for the power
input to the
smart cooling
product. Cut the
37