NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Alarm ID
Alarm Name
A193-01
Air-side diff
pressure sensor
fault
A208-01
Indoor fan 1
blocked alarm
Indoor fan 2
blocked alarm
Indoor fan 3
blocked alarm
Issue 06 (2020-01-13)
Alarm
Impact
Severity
Major
An alarm is
triggered.
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
Major
An alarm is
triggered, and
the
corresponding
fan is shut
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible
Solution
Cause
inlet
into the
solenoid
humidifier
valve are
pan from the
loose or
water inlet
damaged.
pipe of the
humidifier.
5. Verify that
cables to the
water inlet
solenoid
valve are
properly
connected.
1. The
1. Check the
differential
cable
pressure
connection
sensor cable
to the
is loose or
differential
damaged.
pressure
sensor.
2. The pressure
tube of the
2. Check the
differential
tube
pressure
connection
sensor is
to the
reversely
differential
connected.
pressure
sensor.
3. The
differential
3. Maintain or
pressure
replace the
sensor is
differential
faulty.
pressure
sensor.
1. The indoor
1. Clear the
fan blade is
blockage.
stuck.
2. Maintain or
2. The indoor
replace the
fan is faulty.
indoor fan.
1. The indoor
1. Clear the
fan blade is
blockage.
stuck.
2. Maintain or
2. The indoor
replace the
fan is faulty.
indoor fan.
1. The indoor
1. Clear the
fan blade is
blockage.
stuck.
2. Maintain or
2. The indoor
replace the
fan is faulty.
indoor fan.
217