Alarm ID
Alarm Name
A281-40
Power voltage
abnormal
Backup power
voltage
abnormal
A281-80
Power voltage
abnormal
Backup power
voltage
abnormal
Issue 06 (2020-01-13)
Alarm
Impact
Severity
Major
triggered, and
the smart
cooling product
is shut down
when the main
power or single
power is
supplied.
Major
An alarm is
triggered, and
the smart
cooling product
is shut down
when the
standby power
is supplied.
Major
triggered, and
the smart
cooling product
is shut down
when the main
power or single
power is
supplied.
Major
An alarm is
triggered, and
the smart
cooling product
is shut down
when the
standby power
is supplied.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible
Cause
board is
faulty.
1. The power
An alarm is
supply
voltage
exceeds the
upper
threshold.
2. The SPD
and voltage
detection
board is
faulty.
1. The power
supply
voltage
exceeds the
upper
threshold.
2. The SPD
and voltage
detection
board is
faulty.
1. The power
An alarm is
supply
voltage
exceeds the
upper
threshold.
2. The SPD
and voltage
detection
board is
faulty.
1. The power
supply
voltage
exceeds the
upper
threshold.
2. The SPD
and voltage
detection
board is
faulty.
Solution
voltage
detection
board.
1. Check that
the power
supply
voltage is
within the
operating
range.
2. Replace the
SPD and
voltage
detection
board.
1. Check that
the power
supply
voltage is
within the
operating
range.
2. Replace the
SPD and
voltage
detection
board.
1. Check that
the power
supply
voltage is
within the
operating
range.
2. Replace the
SPD and
voltage
detection
board.
1. Check that
the power
supply
voltage is
within the
operating
range.
2. Replace the
SPD and
voltage
detection