Figure 6-5 Removing an upflow differential pressure switch
Figure 6-6 Removing a downflow differential pressure switch
Step 5 Remove the screw from the differential pressure switch cover and take out the cable.
Step 6 Set the new differential pressure switch to 500 Pa, install a new differential pressure switch by
performing
Issue 06 (2020-01-13)
Step 5
to
Step
3, and then close the front door.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
244