NetCol8000-C(070-260) In-room Chilled Water Smart

Cooling Product

User Manual
Figure 3-80 Installing a differential pressure sensor
Step 2 Connect the longer PU hose to the port without the Lo (-) silk screen under the differential
pressure sensor, and route the hose through the top of the cabinet to the supply air pipe static
pressure box. (There should be two binding points adjacent to the pressure inlet. The distance
between the binding point closer to the pressure inlet and the pressure inlet should not exceed
25 mm, and the distance between two binding points is within 20–30 mm.)
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
109