3.2.2 Downflow

Figure 3-9 System layout diagram
(A) Chilled water inlet
(2) Water filter
(5) Chilled water inlet and outlet pipe
connectors
Issue 06 (2020-01-13)
Components shown by (5), (6), and (7) in the preceding figure are delivered with the smart cooling
product. Other components need to be purchased and installed onsite. Do not install the other
components directly under the cabinet.
A water filter with 20 meshes and pressure resistance of 1.6 MPa or higher is recommended onsite.
Pressure resistance of the water filter is determined by site requirements. Install the water filter on
the external water inlet pipe near the smart cooling product.
Components shown by (5), (6), and (7) in the preceding figure are delivered with the smart cooling
product. Other components need to be purchased and installed onsite. Do not install the other
components directly under the cabinet.
A water filter with 20 meshes and pressure resistance of 1.6 MPa or higher is recommended onsite.
Pressure resistance of the water filter is determined by site requirements. Install the water filter on
the external water inlet pipe near the smart cooling product.
Copyright © Huawei Technologies Co., Ltd.
(B) Chilled water
(1) Balance valve or
outlet
isolation valve
(3) Isolation valve
(4) Soft connection
(6) Chilled water
(7) Heat exchanger