Huawei NetCol8000-C User Manual page 238

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C:
Table of Contents

Advertisement

NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Alarm ID
Alarm Name
Return air
damper 1
temp/humid
sensor fault
A27F-01
Water overflow
alarm
Issue 06 (2020-01-13)
Alarm
Impact
Severity
Major
N/A
Critical
An alarm is
triggered, and
all the parts
expect for
indoor fans are
shut down.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible
Solution
Cause
sensor is
faulty.
1. The cables
1. Check the
to the
cables to the
temperature
temperature
and
and
humidity
humidity
sensor are
sensor.
loose or
2. Maintain or
damaged.
replace the
2. The
temperature
temperature
and
and
humidity
humidity
sensor.
sensor is
faulty.
1. The water
1. While
overflow
configuring
sensor
the water
detects water
overflow
or the sensor
sensor,
is faulty.
check and
clear the
2. The drainage
water
filter is
source, and
blocked.
maintain or
3. The
replace the
drainpipe is
sensor.
blocked.
2. Clear the
4. The
foreign
drainpipe is
matter in the
blocked.
water pan
5. The high
and filter.
liquid level
3. Check that
sensor is
the drainpipe
faulty.
is not
blocked or
bent.
4. If the drain
pump is
configured,
check its
cable
connections,
clear the
foreign
matter in it,
or replace it.
5. While
configuring
the high
230