Huawei NetCol8000-C User Manual page 198

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C:
Table of Contents

Advertisement

NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Alarm ID
Alarm Name
Supply water
temperature
sensor fault
Return water
temperature
sensor fault
A002-01
Return air high
temperature
alarm
Issue 06 (2020-01-13)
Alarm
Impact
Severity
Major
An alarm is
triggered.
Major
An alarm is
triggered.
Critical
N/A
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible
Solution
Cause
1. The cables
1. Check the
to the
cables to the
temperature
temperature
sensor are
sensor.
loose or
2. Maintain or
damaged.
replace the
2. The
temperature
temperature
sensor.
sensor is
faulty.
1. The cables
1. Check the
to the
cables to the
temperature
temperature
sensor are
sensor.
loose or
2. Maintain or
damaged.
replace the
2. The
temperature
temperature
sensor.
sensor is
faulty.
1. The
1. Adjust the
temperature
positions of
sensors or
the
temperature
temperature
and
sensors or
humidity
temperature
sensors are
and
located in
humidity
inappropriat
sensors.
e positions.
2. Add smart
2. The thermal
cooling
load power
products or
is high or the
contact
cooling
Huawei
capacity is
technical
insufficient.
support.
3. The ambient
3. Measure the
temperature
ambient
exceeds the
temperature.
upper
Check
threshold.
whether
other causes
4. The high
exist if the
temperature
alarm
alarm
persists in a
threshold is
long time
inappropriat
after startup.
e.
4. Adjust the
5. The value
high
detected by
temperature
the
190