NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Menu
Languag
e
Date &
Time
Settings
Teamwo
rk
Settings
(visible
for
V200R0
02
version)
System
Issue 06 (2020-01-13)
Parameter
Description
Date format
Specifies the date display
format for the ACC.
Date
Specifies the date displayed on
settings
the ACC.
Time
Specifies the time displayed on
the ACC.
Time zone
Specifies the time zone
displayed on the ACC.
Teamwork
Set the assigned teamwork
group No.
control number.
Air
Set the assigned smart cooling
conditioner
product address.
address
Teamwork
Disable or enable the
function
teamwork function. If the
teamwork function is disabled,
this device is operating
according to its own control. If
the teamwork function is
enabled, this device works in
harmony with others that in the
same group.
Networking
Networking mode for the
mode
teamwork. The networking
mode set on the screen must be
consistent with the actual
networking mode. Otherwise,
the teamwork control function
will be unavailable.
Number of
Number of the smart cooling
smart
products in this group (1 to 32
can be set).
cooling
products in
this group
Number of
Number of active units in a
running
group. The value ranges from 1
smart
to Number of smart cooling
cooling
products in this group.
products in
this group
Humidifyin
The humidifying function can
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
the actual situation.
Set the parameter according to
reading habits.
Set the parameter according to
the actual situation.
Set the parameter according to
the actual situation.
Set the parameter according to
the actual situation.
The number of the teamwork
controlled group, which is the
same for all the devices in the
group.
Air conditioner addresses
should be different from each
other.
Set this parameter based on the
onsite device heat distribution.
Networked over CAN or
MAC_CAN. CAN network
indicates teamwork control
over a CAN bus, MAC_CAN
network teamwork control
over an FE port.
Total number of the smart
cooling products in this group.
The host allocates running
units by smart cooling product
unit address in ascending
order, which is from 1 to 32.
The rest will become the
standby ones.
Enable indicates that the
124