NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Menu
Issue 06 (2020-01-13)
Parameter
Description
mode
aisles based on the Average
value, Max value, or Min
value of the temperatures
collected by each sensor.
Temperatur
After the Temperature and
e setpoint
humidity control type and the
temperature value under this
type are set, the device
conducts cooling or heating
based on the settings.
Humidity
After the Temperature and
setpoint
humidity control type and the
humidity value under this type
are set, the device conducts
humidifying or dehumidifying
based on the settings.
Cold aisle
The sensors in cold aisles can
sensor 1
be set to Enable or Disable.
Cold aisle
sensor 2
Cold aisle
sensor 3
Cold aisle
sensor 4
Cold aisle
sensor 5
Hot aisle
The sensors in hot aisles can be
sensor 1
set to Enable or Disable.
Hot aisle
sensor 2
Hot aisle
sensor 3
Hot aisle
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
temperature is to be
controlled based on the
averaged data value
collected by the collector.
Max value: Select Max
value if the temperature is
to be controlled based on
the maximum data value
collected by the collector.
Min value: Select Min
value if the temperature is
to be controlled based on
the minimum data value
collected by the collector.
Set this parameter as required.
Return air temperature:
26–35° C recommended
Supply air temperature:
18–24° C recommended
Cold aisle temperature:
18–24° C recommended
Hot aisle temperature:
26–35° C recommended
Set this parameter as required.
40%–60% RH recommended
The cold aisle sensors outside
the cabinet need to be enabled
when they are installed.
The hot aisle sensors outside
the cabinet need to be enabled
when they are installed.