Setting The Capacity Of A Circuit Breaker - Huawei PowerCube 1000 Installation Manual

Table of Contents

Advertisement

PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide
Procedure
Step 1 Set the usage of the branch based on the device connected to the circuit breaker.
Table 12-4 Setting branch usage parameters on the LCD
Main Menu
Second
-Level
Menu
Parameters
Digital
Settings
Power
----End

12.2.4.2 Setting the Capacity of a Circuit Breaker

You can set the circuit breaker capacity when the circuit breaker usage is set to
load branch (BLVD Load/Customized Load), general power distribution branch
(Power Cascading Port/DC DG/Solar Energy/Other), or battery power distribution
branch (Lithium Battery/Lead-acid Battery).
Issue 02 (2021-09-28)
Customized Load: Set when a device that needs to be configured with a
disconnection mode and disconnection parameter is connected. (The default
disconnection mode is Voltage Mode, and the default disconnection voltage
is 44 V.)
BLVD Load: Set when primary loads are connected.
Power Cascading Port:
Set when a DC power distribution unit (such as iDMU48-300B-17A) that
supports the measurement function is added.
Set when Huawei solar PV distribution units (such as the PVDU-100A1,
PVDU-150A1, PVDU-150A3, and PVDU-200A1) are connected in the solar
access scenario.
DC DG: Set when a DC DG is connected. The circuit breaker can be used to
collect statistics on the DG energy yield.
Solar Energy: Set when a third-party solar power supply unit (48 V power
supply) is connected. The circuit breaker can be used to collect statistics on
solar energy yield.
Lithium Battery: Set based on the connected lithium battery branch.
Lead-acid Battery: Set based on the connected lead-acid battery branch.
Other: Set when other 48 V power supply devices are connected.
Third-Level
Fourth-Level
Menu
Menu
DC Output
Branch Usage
Distribut.
Config 1
Branch Usage
Config 2
Copyright © Huawei Technologies Co., Ltd.
12 Power-on and Commissioning
Fifth-Level
Value Range
Menu
Branch n
Customized Load, BLVD
Usage
Load, Power Cascading
Config
Port, DC DG, Solar Energy,
Lithium Battery, Lead-acid
Branch n
Battery, and Other
Usage
Config