X130 Digital Input (Fail Safe) Digital Output - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Control Units, Control Unit Adapters and operating components
7.4 Control Unit CU310-2 DP (PROFIBUS)
7.4.2.11

X130 digital input (fail safe) digital output

Table 7- 33
X130 digital input / fail-safe digital output
Terminal
1
2
3
4
5
6
7
8
Type: Spring-loaded terminal 1 (Page 371)
Max. cross-section that can be connected: 1.5 mm
DI: Digital input/DO: Digital output
1)
F-DO: Fail-safe digital output
2)
The maximum cable length that can be connected is 30 m.
Fail-safe digital output
The F-DO consists of a high-side switch and a low-side switch.
For applications without the safety function, the high-side switch may be used as an
additional digital output. The low side switch is not available.
Note
If the 24 V supply is briefly interrupted, the digital output is deactivated until the interruption
has been rectified.
258
Designation
Technical data
1)
DI 22+
Voltage: -3 ... 30 VDC
Current consumption, typical: 6 mA at 24 V
DI 22-
Electrical isolation: via optocoupler
Level (incl. ripple)
High level: 15 ... 30 V
Low signal level: -3 ... 5 V (at ≤ 2 mA)
Input delay (typ.):
For "0" → "1": 50 μs
For "1" → "0": 150 μs
protected against polarity reversal
M2
Reference potential for digital inputs DI 0 to DI 3
GND
Ground reference for the electronics
M1
Reference potential for DI 16, DI 18, DI 20 and DO 16
24 V1
Power supply for DO 16
DO 16+
F-DO 0
Voltage: 24 VDC
2)
Max. load current per output: 500 mA
DO 16-
Output delay (typ./max.):
For "0" → "1": 150 µs / 400 μs
For "1" → "0": 75 µs / 100 μs
Short-circuit, ground fault, overload proof
Automatic switch on again after overload trip
2
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
AC Drive

Advertisement

Table of Contents
loading

Table of Contents