Connecting The Dv/Dt Filter With Voltage Peak Limiter - Siemens SINAMICS S120 Manual

Sinamics family modular motion control drives
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor-Side Power Components
5.3 dv/dt filter
5.3.1.4

Connecting the dv/dt filter with Voltage Peak Limiter

Figure 5-15
Connecting the dv/dt filter with Voltage Peak Limiter
Cable cross-sections
Table 5-19
Cable cross-sections for connected between a dv/dt filter and Power Module
dv/dt filter plus Voltage Peak Limiter
6SL3000-2DE32-6AA0
6SL3000-2DE35-0AA0
Note
The connections should be kept as short as possible.
The maximum cable length for the specified connections is is 5 m.
166
Connection to the DC link
(DCPS / DCNS)
[mm²]
35
70
Connection between a dv/dt reactor
and voltage limiting network
(1U2, 1V2, 1W2) [mm²]
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2
10
16
AC Drive