Errors can be acknowledged by pressing the acknowledge button. If an
additional error exists, it is displayed after the first error has been
acknowledged.
More information on EMC and environment/ambient conditions, refer to
the SIMADYN D Hardware Manual, Section "General Technical Data" or
the appropriate SIMATIC S7 documentation!

2.1.6 Technical data

Order No.
Digital inputs
Voltages, currents
Dimensions
Application Module FM 458 - User Manual
6DD1904-0AE0
Edition 12.2001
Application module FM 458
Number
Electrical isolation
Input voltage
Permissible range
Nominal voltage
For a 0 signal
For a 1 signal
Input current
For a 0 signal, typ.
For a 1 signal, typ.
Delay time per channel, max
Rated voltage
Typical current drain
Assignment, slots
Dimensions W x H x D [mm]
Weight
Product description
6DD1607-0AA0
8
No
-1 V to +33 V
24 V
-1 V to + 6 V
+13,5 V to +33 V
0 mA
3 mA
100 µs
+5 V
3,4 V battery
1,8 A
10 µA
1
25 x 290 x 210
0,92 kg