ABB ACS880 Firmware Manual page 109

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
131.10
External event 5
type
Fault
Warning
Pure event
Warning/Fault
131.11
Fault reset selection
Off
On
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
Description
Selects the type of external event 5.
The external event generates a fault.
The external event generates a warning.
The event is only logged with a time stamp. No fault or
warning is generated.
If the DC/DC converter unit is running, the external event
generates a fault. Otherwise, the event generates a
warning.
Selects the source of an external fault reset signal. The
signal resets the DC/DC converter unit after a fault trip if the
cause of the fault no longer exists.
0 - > 1 = Reset
Note: A fault reset from the fieldbus interface is always
observed regardless of this parameter.
Note: Digital inputs and digital input/outputs can be
reserved for use in the control program.
0
1
Digital input DI1 (as indicated by
bit 0).
Note: DI1 is reserved for temperature fault in the control
program. Do not select it for any other use.
Digital input DI2 (as indicated by
bit 1).
Digital input DI3 (as indicated by
bit 2).
Digital input DI4 (as indicated by
bit 3).
Digital input DI5 (as indicated by
bit 4).
Digital input DI6 (as indicated by
bit 5).
Digital input/output DIO1 (as indicated by
delayed
status, bit 0).
Digital input/output DIO2 (as indicated by
delayed
status, bit 1).
Source selection (see
Terms and abbreviations
45).
110.02 DI delayed
status,
110.02 DI delayed
status,
110.02 DI delayed
status,
110.02 DI delayed
status,
110.02 DI delayed
status,
110.02 DI delayed status
111.02 DIO
111.02 DIO
on page
Parameters 109
Def/FbEq16
Fault
0
1
2
3
DI6
0
1
2
3
4
5
6
7
10
11
-