70 Parameters
No.
Name/Value
113.27
AO2 source min
-32768.0 ... 32767.0 Real signal value corresponding to minimum AO2 output
113.28
AO2 source max
-32768.0 ... 32767.0 Real signal value corresponding to maximum AO2 output
113.29
AO2 out at AO2 src
min
0.000 ... 22.000 mA Minimum AO2 output value.
113.30
AO2 out at AO2 src
max
0.000 ... 22.000 mA Maximum AO2 output value.
113.91
AO1 data storage
-327.68 ... 327.67
113.92
AO2 data storage
-327.68 ... 327.67
Description
Defines the real value of the signal (selected by parameter
113.22 AO2
source) that corresponds to the minimum AO2
output value (defined by parameter
src
min).
I
(mA)
AO2
113.30
113.29
113.27
I
(mA)
AO2
113.30
113.29
113.28
value.
Defines the real value of the signal (selected by parameter
113.22 AO2
source) that corresponds to the maximum AO2
output value (defined by parameter
src
max). See parameter
value.
Defines the minimum output value for analog output AO2.
See also drawing at parameter
Defines the maximum output value for analog output AO2.
See also drawing at parameter
Storage parameter for controlling analog output AO1 eg.
through fieldbus.
In
113.12 AO1
source, select
this parameter as the target of the incoming value data.
Storage parameter for AO1.
Storage parameter for controlling analog output AO2 eg.
through fieldbus.
In
113.22 AO2
source, select
this parameter as the target of the incoming value data.
Storage parameter for AO2.
113.29 AO2 out at AO2
113.28
Signal (real)
selected by par.
113.27
Signal (real)
selected by par.
113.30 AO2 out at AO2
113.27 AO2 source
min.
113.27 AO2 source
113.27 AO2 source
AO1 data
storage. Then set
AO2 data
storage. Then set
Def/FbEq16
0.0
113.22
113.22
1 = 1
100.0
1 = 1
4.000 mA
min.
1000 = 1 mA
20.000 mA
min.
1000 = 1 mA
0.00
100 = 1
0.00
100 = 1