ABB ACS880 Firmware Manual page 185

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Fault
(hex)
4E04
Excess temperature
difference
4E06
Cabinet temperature
fault
4E07
Control board
temperature
4E09
Ambient temperature
4E0A
PCB space cooling
5E00
Fan
5E03
XSTO circuit open
5E04
PU logic error
Cause
High temperature difference
between the semiconductors of
different phases. The amount
of available temperatures
depends on the frame size.
A measurement device
connected to supply unit digital
input or DI1 has tripped to a
fault. Input is selected with
parameter
131.33 Cabinet
temperature fault
source.
Excessive temperature of the
busbars/fuses due to cabinet
fan failure.
Excessive temperature of the
chokes inside the DC/DC
converter module due to a
phase loss.
Excessive temperature of the
heat sink of the DC/DC
converter module due to
module fan failure.
(Control program generates
first a warning, then a fault.)
High control board tempera-
ture.
Redundant measurement
supervision has indicated a
difference in the duplicated
measurements that is outside
the limits.
Temperature difference
between ambient and
converter module PCB space
has exceeded the fault limit.
Cooling fan stuck or
disconnected.
Circuit connected to XSTO:IN1
and/or XSTO:IN2 is open.
The memory of the power unit
logic is cleared.
Fault tracing 185
What to do
See
AE15 Excess temperature difference
(page 177).
Check parameter
131.34 Delay cabinet
temp
supervision.
Check cabinet temperature source.
Replace the cabinet fan.
Check the input fuses and the input
connection.
Replace the module fan.
Check proper cooling of the cabinet.
Contact your local ABB representative.
Check the cooling fan inside the PCB
space.
See
AE73 Fan
(page 182).
Check XSTO circuit connections.
See section
Default I/O connection
diagram (BCU)
on page 41.
For more information, see appropriate
hardware manual.
Contact your local ABB representative.