188 Fault tracing
Code
Fault
(hex)
6E05
Internal file load
6E06
Internal record load
6E07
Application loading
6E08
Memory unit detached The memory unit was detached
6E0A
User set fault
6E0B
Kernel overload
6E0C
Parameter system
6E0D
FBA A parameter
conflict
6E0E
FBA B parameter
conflict
6E15
Text data overflow
6E16
Text 32-bit table
overflow
6E17
Text 64-bit table
overflow
6E18
Text file overflow
6E1A
Rating ID fault
6E1B
Backup/Restore
Timeout
Cause
File read error.
Note: This fault cannot be
reset.
Internal record load error.
Application file incompatible or
corrupted.
Note: This fault cannot be
reset.
when the control unit was
powered.
Loading of the user parameter
set failed because
• requested set does not exist
• set is not compatible with the
control program
• converter was switched off
during loading.
Operating system error.
Note: This fault cannot be
reset.
Parameter load or save failed.
The DC/DC converter unit
does not have a functionality
requested by PLC, or
requested functionality has not
been activated.
The DC/DC converter unit
does not have a functionality
requested by PLC, or
requested functionality has not
been activated.
Internal fault.
Internal fault.
Internal fault.
Internal fault.
Rating ID load error.
A control panel or PC tool fails
to communicate with the
converter during backup or
restoring operation.
What to do
Reboot the control unit (using parameter
196.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Switch off the power to the control unit
and reinstall the memory unit.
In case the memory unit was not actually
removed when the fault occurred, check
that the memory unit is properly inserted
into its connector and its mounting screw
is tight. Reboot the control unit (using
parameter
196.08 Control board
by cycling power. If the problem persists,
contact your local ABB representative.
Ensure that a valid user parameter set
exists. Reload.
Contact your local ABB representative.
Try forcing a save using parameter
196.07 Param
save. Retry.
Check PLC programming.
Check settings of parameter groups
FBA
and
151 FBA A
settings.
Check PLC programming.
Check settings of parameter groups
FBA
and
154 FBA B
settings.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Contact your local ABB representative.
Check the control panel or PC tool
communication, and if it is still in
backup/restore state.
boot) or
150
150