Fault Messages - ABB ACS880 Firmware Manual

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Fault messages

Code
Fault
(hex)
2E00
Overcurrent
2E02
Short circuit
2E04
IGBT overload
2E05
BU current difference
2E08
External earth fault
2E0C
User current fault
3E00
Input phase loss
Programmable fault:
131.21 Supply phase loss
3E04
DC link overvoltage
Cause
Too high inverter load or short
circuit.
DC/DC converter has detected
short circuit.
Excessive IGBT junction to
case temperature.
Phase current difference
between parallel-connected
modules.
External earth fault trigged by
input selected with parameter
131.28 Ext earth leakage
signal
source.
Sum current of the three
phases has exceeded the limit
defined with parameter
131.25
User current fault
limit.
Input phase loss detected by
the IGBT bridge.
Excessive intermediate circuit
DC voltage
Fault tracing 183
What to do
Check the load and busbars.
Check supply cable.
Check there are no power factor
correction capacitors or surge absorbers
in supply cable.
Check the auxiliary code (format XXXY
YYZZ). With parallel-connected modules,
"Y YY" specifies through which BCU
control unit channel the fault was
received. "ZZ" indicates the location of
the short circuit (0: No detailed
information available, 1: Upper branch of
U-phase, 2: Lower branch of U-phase,
4: Upper branch of V-phase, 8: Lower
branch of V-phase, 10: Upper branch of
W-phase, 20: Lower branch of W-phase,
other: combinations of the above).
After correcting the cause of the fault,
reboot the control unit (using parameter
196.08 Control board
boot) or by cycling
power.
Check the load.
Check cable connections.
Check mains supply and fuses.
Check external earth fault source.
Usually only one device is allowed in the
same network.
Check the value of parameter
User current fault
limit.
Check current limits of parameters
130.119 Minimum current
Maximum
current.
Check that the DC bus voltage is not
dropping (against the energy storage
voltage) so that the current can flow
uncontrolled from the energy storage to
the DC bus via the freewheeling diodes.
Check the AC fuses.
Check for input power supply imbalance.
Check that parameter
195.01 Supply
voltage
is set according to the supply
voltage in use.
With parallel-connected modules,
check the auxiliary code (format XXXY
YYZZ). "Y YY" specifies through which
BCU control unit channel the fault was
received.
131.25