ABB ACS880 Firmware Manual page 187

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Fault
(hex)
5E0A
Measurement circuit
ADC
5E0B
PU board powerfail
5E0D
PU communication
configuration
5E0F
PU state feedback
5E10
Charging feedback
5E11
Unknown PU fault
5E13
Auxiliary circuit
breaker fault
5E14
Measurement circuit
temperature
6E00
FPGA version
incompatible
6E01
FBA A mapping file
6E02
FBA B mapping file
6E03
Task overload
6E04
Stack overflow
Cause
Measurement circuit analog-to-
digital converter fault.
Power unit power supply
failure.
Version check cannot find a
matching power unit FPGA
logic, or there are more
modules connected than
specified for current rating id.
State feedback from output
phases does not match control
signals.
Incorrect parameter setting.
The charging switch and DC
switch were operated out of
sequence, or a start command
was issued before the unit was
ready.
Charging circuit fault.
Unidentified power unit logic
fault.
Circuit breaker fault trigged by
input selected with parameter
131.32 Aux circuit breaker fault
source.
Problem with internal
temperature measurement of
the converter.
Firmware and FPGA versions
are incompatible.
Fieldbus adapter A mapping
file read error.
Fieldbus adapter B mapping
file read error.
Internal fault.
Note: This fault cannot be
reset.
Internal fault.
Note: This fault cannot be
reset.
Fault tracing 187
What to do
Contact your local ABB representative.
Check the auxiliary code (format ZZZY
YYXX). "YY Y" specifies the affected
module (0...C). "XX" specifies the
affected power supply (1: Power
supply 1, 2: Power supply 2).
If the number of modules is correct,
update the FPGA logic of the power unit.
Contact your local ABB representative.
Contact your local ABB representative.
Check the setting of
195.09 Fuse switch
control. The parameter should be
enabled only if an xSFC charging
controller is installed.
The normal power-up sequence is:
1. Close charging switch.
2. After charging finishes (charging OK
lamp lights), close DC switch.
3. Open charging switch.
Check the charging circuit.
Check the logic and firmware
compatibility.
Contact your local ABB representative.
By default the feedback is connected to
DI4.
Contact your local ABB representative.
Update power unit FPGA logic or
firmware (whichever is older).
Reboot the control unit (using parameter
196.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Reboot the control unit (using parameter
196.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Reboot the control unit (using parameter
196.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.