180 Fault tracing
Code
Warning
(hex)
AE49
Value counter 1
warning
(Editable message
text)
Programmable
warning:
133.55 Value counter 1
warning select
AE4A
Value counter 2
warning
(Editable message
text)
Programmable
warning:
133.65 Value counter 2
warning selection
AE51
External warning 1
Programmable warning:
131.01 External event 1
source
131.02 External event 1
type
AE52
External warning 2
(Editable message
text)
Programmable
warning:
131.03 External event 2
source
131.04 External event 2
type
AE53
External warning 3
(Editable message
text)
Programmable
warning:
131.05 External event 3
source
131.06 External event 3
type
AE54
External warning 4
(Editable message
text)
Programmable
warning:
131.07 External event 4
source
131.08 External event 4
type
AE55
External warning 5
(Editable message
text)
Programmable
warning:
131.09 External event 5
source
131.10 External event 5
type
AE57
Autoreset
Cause
Warning generated by value
counter 1.
Warning generated by value
counter 2.
Fault in external device 1.
Fault in external device 2.
Fault in external device 3.
Fault in external device 4.
Fault in external device 5.
A fault is about to be autoreset. Informative warning. See the settings in
What to do
Check the source of the warning
(parameter
133.53 Value counter 1
source).
Check the source of the warning
(parameter
133.63 Value counter 2
source).
Check the external devices.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
Check the external device.
Check setting of parameter
External event 3
source.
Check the external device.
Check setting of parameter
External event 4
source.
Check the external device.
Check setting of parameter
External event 5
source.
parameter group
131 Fault
131.01
131.03
131.05
131.07
131.09
functions.