124 Parameters
No.
Name/Value
149.03
Baud rate
9.6 kbps
38.4 kbps
57.6 kbps
86.4 kbps
115.2 kbps
230.4 kbps
460.8 kbps
921.6 kbps
149.04
Communication loss
time
0.3 ... 3000.0 s
149.05
Communication loss
action
No action
Fault
149.06
Refresh settings
Done
Configure
150

150 FBA

150.01
FBA A Enable
Disable
Option slot 1
Option slot 2
Option slot 3
150.02
FBA A comm loss
func
No action
Fault
Fault always
Description
Defines the transfer rate of the link.
Note: If you change the setting, new setting takes effect
only after parameter
149.06 Refresh settings
Done.
9.6 kbit/s.
38.4 kbit/s.
57.6 kbit/s.
86.4 kbit/s.
115.2 kbit/s.
230.4 kbit/s.
460.8 kbit/s.
921.6 kbit/s.
Sets a time-out for control panel (or PC tool)
communication. If a communication break lasts longer than
the time-out, the action specified by parameter
Communication loss action
Panel/PC tool communication time-out.
Selects how the DC/DC converter unit reacts to a control
panel (or PC tool) communication break.
Note: If you change the setting, new setting takes effect
only after parameter
149.06 Refresh settings
Done.
Communication break does not cause any actions.
DC/DC converter unit trips on a fault
the motor coasts to a stop.
Applies the settings of parameters 149.01...149.05.
Note: Refreshing may cause a communication break, so
reconnecting may be required.
Refresh done or not requested.
Refresh parameters 149.01...149.05. The value reverts
automatically to Done.
General settings for fieldbus communication configuration.
Enables/disables communication between the DC/DC
converter unit and fieldbus adapter A, and specifies the slot
the adapter is installed into.
Communication between DC/DC converter unit and fieldbus
adapter A disabled.
Communication between DC/DC converter unit and fieldbus
adapter A enabled. The adapter is in slot 1.
Communication between DC/DC converter unit and fieldbus
adapter A enabled. The adapter is in slot 2.
Communication between DC/DC converter unit and fieldbus
adapter A enabled. The adapter is in slot 3.
Selects how the DC/DC converter unit reacts upon a
fieldbus communication break. The time delay is defined by
parameter
150.03 FBA A comm loss t
Communication break detection disabled.
Communication break detection active. Upon a
communication break, the DC/DC converter unit trips on a
communication fault.
The DC/DC converter unit trips on a communication fault
even though no control is expected from the fieldbus.
is switched to
149.05
is taken.
is switched to
7E01 Panel loss
out.
Def/FbEq16
230.4 kbps
0
1
2
3
4
5
6
7
10.0 s
10 = 1 s
Fault
0
and
1
Done
0
1
Disable
0
1
2
3
No action
0
1
4