ABB ACS880 Firmware Manual page 127

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
150.31
FBA B Enable
Disable
Option slot 1
Option slot 2
Option slot 3
150.32
FBA B comm loss
func
No action
Fault
Fault always
Warning
150.33
FBA B comm loss
timeout
0.3 ... 6553.5 s
150.34
FBA B ref1 type
150.35
FBA B ref2 type
150.37
FBA B act1 type
150.38
FBA B act2 type
150.40
FBA B act1
transparent source
Not selected
Other [bit]
150.41
FBA B act2
transparent source
Not selected
Other [bit]
Description
Enables/disables communication between the DC/DC
converter unit and fieldbus adapter B, and specifies the slot
the adapter is installed into.
Communication between DC/DC converter unit and fieldbus
adapter B disabled.
Communication between DC/DC converter unit and fieldbus
adapter B enabled. The adapter is in slot 1.
Communication between DC/DC converter unit and fieldbus
adapter B enabled. The adapter is in slot 2.
Communication between DC/DC converter unit and fieldbus
adapter B enabled. The adapter is in slot 3.
Selects how the DC/DC converter unit reacts upon a
fieldbus communication break. The time delay is defined by
parameter
150.33 FBA B comm loss
Communication break detection disabled.
Communication break detection active. Upon a
communication break, the DC/DC converter unit trips on a
communication fault.
The DC/DC converter unit trips on a communication fault
even though no control is expected from the fieldbus.
The DC/DC converter unit generates a communication
warning even though no control is expected from the
fieldbus.
Defines the time delay before the action defined by
parameter
150.32 FBA B comm loss func
count starts when the communication link fails to update the
message.
Time delay.
Selects the type and scaling of reference 1 received from
fieldbus adapter B.
For the selections, see parameter
Selects the type and scaling of reference 2 received from
fieldbus adapter B.
For the selections, see parameter
Selects the type and scaling of actual value 1 transmitted to
the fieldbus network through fieldbus adapter B.
For the selections, see parameter
Selects the type and scaling of actual value 2 transmitted to
the fieldbus network through fieldbus adapter B.
For the selections, see parameter
When parameter
150.37 FBA B act1 type
Transparent, this parameter selects the source of actual
value 1 transmitted to the fieldbus network through fieldbus
adapter B.
No source selected.
Source selection (see
Terms and abbreviations
45).
When parameter
150.38 FBA B act2 type
Transparent, this parameter selects the source of actual
value 2 transmitted to the fieldbus network through fieldbus
adapter B.
No source selected.
Source selection (see
Terms and abbreviations
45).
Parameters 127
timeout.
is taken. Time
150.04 FBA A ref1
type.
150.05 FBA A ref2
type.
150.07 FBA A act1
type.
150.07 FBA A act1
type.
is set to
on page
is set to
on page
Def/FbEq16
Disable
0
1
2
3
No action
0
1
4
5
0.3 s
10 = 1 s
Active power
Active power
Transparent
Transparent
Not selected
-
-
Not selected
-
-