Fba B Data In; Fba B Data Out - ABB ACS880 Firmware Manual

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

132 Parameters
No.
Name/Value
154.32
FBA B comm SW
ver
154.33
FBA B appl SW ver
155

155 FBA B data in

155.01
FBA B data in1
None
CW 16bit
Ref1 16bit
Ref2 16bit
SW 16bit
Act1 16bit
Act2 16bit
CW 32bit
SW 32bit
Act1 32bit
Act2 32bit
Other
...
...
155.12
FBA B data in12
156

156 FBA B data out

156.01
FBA B data out1
None
CW 16bit
Ref1 16bit
Ref2 16bit
CW 32bit
Other
...
...
156.12
FBA B data out12
Description
Displays the common program revision of the adapter
module in format axyz, where a = major revision number, xy
= minor revision number, z = correction number.
Example: 190A = revision 1.90A.
Common program revision of adapter module.
Displays the application program revision of the adapter
module in format axyz, where a = major revision number, xy
= minor revision number, z = correction number or letter.
Example: 190A = revision 1.90A.
Application program version of adapter module.
Selection of data to be transferred from the DC/DC
converter unit to fieldbus controller through fieldbus adapter
B.
Note: 32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
155.01...155.12
from the DC/DC converter unit to the fieldbus controller
through fieldbus adapter B.
None.
Control word (16 bits)
Reference REF1 (16 bits)
Reference REF2 (16 bits)
Status word (16 bits)
Actual value ACT1 (16 bits)
Actual value ACT2 (16 bits)
Control word (32 bits)
Status word (32 bits)
Actual value ACT1 (32 bits)
Actual value ACT2 (32 bits)
The value is taken from another parameter.
...
See parameter
155.01 FBA B data in1.
Selection of data to be transferred from fieldbus controller to
the DC/DC converter unit through fieldbus adapter B.
Note: 32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
156.01...156.12
from the fieldbus controller to the DC/DC converter unit
through fieldbus adapter B.
None.
Control word (16 bits)
Reference REF1 (16 bits)
Reference REF2 (16 bits)
Control word (32 bits)
The value is taken from another parameter.
...
See parameter
156.01 FBA B data
select data to be transferred
select data to be transferred
out1.
Def/FbEq16
-
1 = 1
-
1 = 1
None
0
1
2
3
4
5
6
11
14
15
16
-
None
None
0
1
2
3
11
-
...
None