Fba B Settings - ABB ACS880 Firmware Manual

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
154

154 FBA B settings

154.01
FBA B type
154.02
FBA B Par2
0...65535
...
...
154.26
FBA B Par26
0...65535
154.27
FBA B par refresh
Done
Configure
154.28
FBA B par table ver
154.29
FBA B drive type
code
0...65535
154.30
FBA B mapping file
ver
0...65535
154.31
D2FBA B comm sta
Idle
Exec.init
Time out
Conf.err
Off-line
On-line
Reset
Description
Fieldbus adapter B configuration.
Displays the type of the connected fieldbus adapter module.
0 = Module is not found or is not properly connected, or is
disabled by parameter
150.31 FBA B
32 = FCAN; 37 = FDNA; 101 = FCNA; 128 = FENA-11/21;
132 = PROFINET IO; 135 = FECA; 136 = FEPL;
485 = FSCA; 62944 = FSEA.
Note: All types of the fieldbus adapter modules are not
necessarily supported yet.
This parameter is read-only.
Parameters
154.02...154.26
For more information, see the documentation of the fieldbus
adapter module. Note that not all of these parameters are
necessarily used.
Fieldbus adapter configuration parameter.
...
See parameter
154.26 FBA B
Fieldbus adapter configuration parameter.
Validates any changed fieldbus adapter module
configuration settings. After refreshing, the value reverts
automatically to Done.
Note: This parameter cannot be changed while the DC/DC
converter unit is running.
Refreshing done.
Refreshing.
Displays the parameter table revision of the fieldbus adapter
module mapping file stored in the memory.
In format axyz, where a = major revision number; xy = minor
revision number; z = correction number.
Parameter table revision of adapter module.
Displays the type code of the fieldbus adapter module
mapping file stored in the memory.
Type code of fieldbus adapter module mapping file.
Displays the fieldbus adapter module mapping file revision
stored in the memory of the DC/DC converter unit in
decimal format.
Example: Integer 263 -> 0x107 = revision 1.07
Mapping file revision.
Displays the status of the fieldbus adapter module
communication.
Adapter is not configured.
Adapter is initializing.
A time-out has occurred in the communication between the
adapter and the DC/DC converter unit.
Adapter configuration error: the major or minor revision
code of the common program revision in the fieldbus
adapter module is not the revision required by the module
(see parameter
154.32 FBA B comm SW
file upload has failed more than three times.
Adapter is off-line.
Adapter is on-line.
Adapter is performing a hardware reset.
Enable; 1 = FPBA;
are adapter module-specific.
Par2.
ver), or mapping
Parameters 131
Def/FbEq16
-
-
1 = 1
...
-
1 = 1
Done
0
1
-
1 = 1
-
1 = 1
-
1 = 1
Idle
0
1
2
3
4
5
6