126 Parameters
No.
Name/Value
150.13
FBA A Control Word
00000000h ...
FFFFFFFFh
150.14
FBA A Reference
REF1
-2147483648 ...
2147483647
150.15
FBA A Reference
REF2
-2147483648 ...
2147483647
150.16
FBA A Status Word
00000000h ...
FFFFFFFFh
150.17
FBA A Actual
value 1
-2147483648 ...
2147483647
150.18
FBA A Actual
value 2
-2147483648 ...
2147483647
150.21
FBA A Timelevel sel
Normal
Fast
Very fast
Monitoring
Description
Displays the control word received from fieldbus adapter A.
For the commands assigned to each bit, see chapter
Fieldbus control through a fieldbus
Control word received from fieldbus adapter A.
Displays raw (unmodified) reference REF1 sent by the
master (PLC) to fieldbus adapter A if debugging is enabled
by parameter
150.12 FBA A debug
This parameter is read-only.
Raw REF1 sent by master to fieldbus adapter A.
Displays raw (unmodified) reference REF2 sent by the
master (PLC) to fieldbus adapter A if debugging is enabled
by parameter
150.12 FBA A debug
This parameter is read-only.
Raw REF2 sent by master to fieldbus adapter A.
Displays the status word sent to fieldbus adapter A. For the
commands assigned to each bit, see chapter
control through a fieldbus
Status word sent to fieldbus adapter A.
Displays raw actual value ACT1 sent to fieldbus adapter A.
Raw ACT1 sent to fieldbus adapter A.
Displays raw actual value ACT2 sent to fieldbus adapter A.
Raw ACT2 sent to fieldbus adapter A.
Selects the communication speed for the fieldbus adapter
A.
In general, lower speeds reduce CPU load. The table below
shows the read/write intervals for cyclic and acyclic data
with each parameter setting.
Selection
Cyclic*
Monitoring
10 ms
Normal
2 ms
Fast
500 µs
Very fast
250 µs
*Cyclic data consists of fieldbus Control and Status words,
Act1 and Act2.
**Acyclic data consists of the parameter data mapped to
parameter groups
152 FBA A data in
out.
Normal speed.
Fast speed.
Very fast speed.
Low speed. Optimized for PC tool communication and
monitoring usage.
adapter.
mode.
mode.
Fieldbus
adapter.
Acyclic**
10 ms
10 ms
2 ms
500 µs
and
153 FBA A data
Def/FbEq16
-
1 = 1
-
-
-
-
-
1 = 1
-
1 = 1
-
1 = 1
Normal
0
1
2
3