86 Parameters
No.
Name/Value
114.88
AO2 force data
0.000 ... 22.000 mA Forced value of analog output AO2.
114.89
AO2 filter time
0.000 ... 30.000 s
114.90
AO2 source min
-32768.0 ... 32767.0 Real signal value corresponding to minimum AO2 output
Description
(Visible when
114.01 Module 1 type
Forced value that can be used instead of the selected
output signal. See parameter
(Visible when
114.01 Module 1 type
Defines the filtering time constant for analog output AO2.
%
100
63
T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Filter time constant.
(Visible when
114.01 Module 1 type
Defines the real value of the signal (selected by parameter
114.87 AO2
source) that corresponds to the minimum AO2
output value (defined by parameter
src
min).
I
(mA)
AO2
114.93
114.92
114.90
I
(mA)
AO2
114.93
114.92
114.91
value.
= FAIO-01)
114.71 AO force
selection.
= FAIO-01)
Unfiltered signal
Filtered signal
t
-t/T
)
= FAIO-01)
114.92 AO2 out at AO2
114.91
Signal (real)
selected by par.
114.90
Signal (real)
selected by par.
Def/FbEq16
0.000 mA
1000 = 1 mA
0.100 s
1000 = 1 s
0.0
114.87
114.87
1 = 1