VLT
HVAC Drive Programming Guide
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. 8-01
8-53 Start Select
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. 8-01
8-54 Reversing Select
Option:
[0] *
Digital input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
NB!
This parameter is active only when par. 8-01
8-55 Set-up Select
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
Control Site
is set to [0]
Function:
Select control of the frequency converter start function via the terminals (digital input) and/or via
the fieldbus.
Activates Start command via a digital input.
Activates Start command via the serial communication port or fieldbus option.
Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
Control Site
is set to [0]
Function:
Select control of the frequency converter reverse function via the terminals (digital input) and/or
via the fieldbus.
Activates Reverse command via a digital input.
Activates Reverse command via the serial communication port or fieldbus option.
Activates Reverse command via the fieldbus/serial communication port, AND additionally via one of
the digital inputs.
Activates Reverse command via the fieldbus/serial communication port OR via one of the digital
inputs.
Control Site
is set to [0]
Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via
the fieldbus.
Activates the set-up selection via a digital input.
Activates the set-up selection via the serial communication port or fieldbus option.
Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one
of the digital inputs.
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Digital and control word
.
Digital and control word
.
Digital and control word
.
3
111