VLT
HVAC Drive Programming Guide
0-50 LCP Copy
Option:
[0] *
No copy
[1]
All to LCP
[2]
All from LCP
[3]
Size indep. from LCP
This parameter cannot be adjusted while the motor is running.
0-51 Set-up Copy
Option:
[0] *
No copy
[1]
Copy to set-up 1
[2]
Copy to set-up 2
[3]
Copy to set-up 3
[4]
Copy to set-up 4
[9]
Copy to all
3.2.8 0-6* Password
Define password access to menus.
0-60 Main Menu Password
Range:
100 N/A*
[0 - 999 N/A]
0-61 Access to Main Menu w/o Password
Option:
[0] *
Full access
[1]
Read only
[2]
No access
Full access
If
[0] is selected then par. 0-60
Password
will be ignored.
0-65 Personal Menu Password
Range:
200 N/A*
[0 - 999 N/A]
Function:
No function
Copies all parameters in all set-ups from the frequency converter memory to the LCP memory. For
service purposes it is recommended to copy all parameters to the LCP after commissioning.
Copies all parameters in all set-ups from the LCP memory to the frequency converter memory.
Copies only the parameters that are independent of the motor size. The latter selection can be used
to programme several frequency converters with the same function without disturbing motor data
which are already set.
Function:
No function
Copies all parameters in the present Programming Set-up (defined in par. 0-11
up
) to Set-up 1.
Copies all parameters in the present Programming Set-up (defined in par. 0-11
up
) to Set-up 2.
Copies all parameters in the present Programming Set-up (defined in par. 0-11
up
) to Set-up 3.
Copies all parameters in the present Programming Set-up (defined in par. 0-11
up
) to Set-up 4.
Copies the parameters in the present set-up over to each of the set-ups 1 to 4.
Function:
Define the password for access to the Main Menu via the [Main Menu] key. If par. 0-61
Main Menu w/o Password
is set to
Function:
Disables password defined in par. 0-60
Prevent unauthorized editing of Main Menu parameters.
Prevent unauthorized viewing and editing of Main Menu parameters.
Main Menu Password
Personal Menu Password
, par. 0-65
Function:
Define the password for access to the My Personal Menu via the [Quick Menu] key. If
Access to Personal Menu w/o Password
par. 0-66
ignored.
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Full access
[0], this parameter will be ignored.
Main Menu Password
.
Access to Personal Menu w/o
and par. 0-66
Full access
is set to
3
Programming Set-
Programming Set-
Programming Set-
Programming Set-
Access to
[0], this parameter will be
45
Need help?