Quick Setup Parameters - Danfoss VLT Programming Manual

Hvac drive
Hide thumbs Also See for VLT:
Table of Contents

Advertisement

®
VLT
HVAC Drive Programming Guide
Illustration 2.6: Quick Menu view.
The Quick Setup menu gives access to the 18 most important setup parameters of the frequency converter. After programming the frequency converter
will, in most cases, be ready for operation. The 18 Quick Setup parameters are shown in the table below. A complete description of the function is given
in the parameter description sections of this manual.
Parameter
Language
Par. 0-01
Motor Power [kW]
Par. 1-20
Par. 1-21
Motor Power [HP]
Par. 1-22
Motor Voltage
*
Par. 1-23
Motor Frequency
Motor Current
Par. 1-24
Motor Nominal Speed
Par. 1-25
Motor Rotation Check
Par. 1-28
Ramp 1 Ramp Up Time
Par. 3-41
Par. 3-42
Ramp 1 Ramp Down Time
Par. 4-11
Motor Speed Low Limit [RPM]
Motor Speed Low Limit [Hz]
Par. 4-12
Motor Speed High Limit [RPM]
Par. 4-13
Motor Speed High Limit [Hz]
Par. 4-14
Jog Speed [RPM]
Par. 3-19
Par. 3-11
Jog Speed [Hz]
*
Par. 5-12
Terminal 27 Digital Input
Par. 5-40
Function Relay
**
Table 2.1: Quick Setup parameters
*The display showing depends on choices made in par. 0-02
Speed Unit
Regional Settings
and par. 0-03
required.
** Par. 5-40
Function Relay
, is an array, where one may choose between Relay1 [0] or Relay2 [1]. Standard setting is Relay1 [0] with the default choice
Alarm [9].
See the parameter description in the section
For a detailed information about settings and programming, please see the
x=version number
NB!
If [No Operation] is selected in par. 5-12
If [Coast Inverse] (factory default value) is selected in par. 5-12
start.
[Units]
[kW]
[HP]
[V]
[Hz]
[A]
[RPM]
[Hz]
[s]
[s]
[RPM]
*
[Hz]
[RPM]
*
[Hz]
[RPM]
[Hz]
Motor Speed Unit
depend on which region of the world the frequency converter is supplied to but can be re-programmed as
Commonly Used Parameters
.
VLT HVAC Drive Programming Guide, MG.11.CX.YY
Terminal 27 Digital Input
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
Regional Settings
and par. 0-03
. The default settings of par. 0-02
y=language
, no connection to +24 V on terminal 27 is necessary to enable start.
Terminal 27 Digital Input
, a connection to +24V is necessary to enable
2 How to Programme
2
Motor
23