HVAC Drive Programming Guide
21-13 Ext. 1 Reference Source
Option:
[0] *
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital pot.meter
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3
21-14 Ext. 1 Feedback Source
Option:
[0] *
No function
[1]
Analog input 53
[2]
Analog input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[100]
Bus feedback 1
[101]
Bus feedback 2
[102]
Bus feedback 3
21-15 Ext. 1 Setpoint
Range:
0.000
Ex-
[-999999.999 - 999999.999 Ex-
tPID1Unit*
tPID1Unit]
21-17 Ext. 1 Reference [Unit]
Range:
0.000
Ex-
[-999999.999 - 999999.999 Ex-
tPID1Unit*
tPID1Unit]
Function:
This parameter defines which input on the frequency converter should be treated as the source of
the reference signal for the Closed Loop 1 Controller. Analog input X30/11 and Analog input X30/12
refer to inputs on the General Purpose I/O.
Function:
This parameter defines which input on the frequency converter should be treated as the source of
the feedback signal for the Closed Loop 1 controller. Analog input X30/11 and Analog input X30/12
refer to inputs on the General Purpose I/O .
Function:
The setpoint reference is used in extended 1 closed loop. Ext.1 Setpoint is added to the value from
the Ext.1 Reference source selected in par. 21-13
Function:
Readout of the reference value for the Closed Loop 1 Controller.
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Ext. 1 Reference Source
.
3
193