3 Parameter Description
[9] *
Active Set-up
This parameter is unique to LCP and fieldbuses. See also par. 0-11

9-71 Profibus Save Data Values

Option:
3
[0] *
Off
[1]
Store all setups
[2]
Store all setups

9-72 ProfibusDriveReset

Option:
[0] *
No action
[1]
Power-on reset
[3]
Comm option reset

9-80 Defined Parameters (1)

Array [116]
No LCP access
Read only
Range:
0 N/A*
[0 - 9999 N/A]
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
Range:
0 N/A*
[0 - 9999 N/A]
9-82 Defined Parameters (3)
Array [116]
No LCP access
Read only
Range:
0 N/A*
[0 - 9999 N/A]
122
Follows the active set-up selected in par. 0-10
Programming Set-up
.
Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
Deactivates the non-volatile storage function.
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
Function:
Resets frequency converter upon power-up, as for power-cycle.
Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g.
Node Address
par. 9-18
.
When reset, the frequency converter disappears from the fieldbus, which may cause a communi-
cation error from the master.
Function:
This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
Function:
This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
Function:
This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
Active Set-up
.

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents

Save PDF