3 Parameter Description
1-58 Flystart Test Pulses Current
Range:
30 %*
[0 - 200 %]
1-59 Flystart Test Pulses Frequency
Range:
3
200 %*
[0 - 500 %]
3.3.5 1-6* Load Depend. Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Range:
100 %*
[0 - 300 %]
1-61 High Speed Load Compensation
Range:
100 %*
[0 - 300 %]
54
Function:
Control the percentage of the magnetizing current. The parameter is active when par. 1-73
Start
is enabled. This parameter is only available in VVC+.
Function:
Control the percentage of the frequency of the test pulses. The parameter is active when
Flying Start
par. 1-73
is enabled. This parameter is only available in VVC+.
Function:
Enter the % value to compensate voltage in relation to load when the motor is running at low speed
and obtain the optimum U/f characteristic. The motor size determines the frequency range within
which this parameter is active.
Motor size
0.25 kW - 7.5 kW
11 kW - 45 kW
55 kW - 550 kW
Function:
Enter the % value to compensate voltage in relation to load when the motor is running at high speed
and obtain the optimum U/f characteristic. The motor size determines the frequency range within
which this parameter is active.
Motor size
0.25 kW - 7.5 kW
11 kW - 45 kW
55 kW - 550 kW
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
Change over
< 10 Hz
< 5 Hz
< 3-4 Hz
Change-over
> 10 Hz
< 5 Hz
< 3-4 Hz
Flying