Danfoss VLT Programming Manual page 195

Hvac drive
Hide thumbs Also See for VLT:
Table of Contents

Advertisement

®
VLT
HVAC Drive Programming Guide
21-24 Ext. 1 Dif. Gain Limit
Range:
5.0 N/A*
[1.0 - 50.0 N/A]
3.19.5 21-3* Closed Loop 2 Ref/Fb
Configure Extended Closed Loop 2 Controller reference and feedback.
21-30 Ext. 2 Ref./Feedback Unit
Option:
[0]
[1] *
%
[5]
PPM
[10]
1/min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[75]
mm Hg
[80]
kW
[120]
GPM
[121]
gal/s
[122]
gal/min
[123]
gal/h
[124]
CFM
[125]
ft³/s
Function:
Set a limit for the differentiator gain (DG). The DG will increase if there are fast changes. Limit the
DG to obtain a pure differentiator gain at slow changes and a constant differentiator gain where
quick changes occur.
Function:
See par. 21-10
Ext. 1 Ref./Feedback Unit
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
for details