VLT
HVAC Drive Programming Guide
25-58 Run Next Pump Delay
Range:
0.1 s*
[0.1 - 5.0 s]
25-59 Run on Mains Delay
Range:
0.5 s*
[Application dependant]
3.23.6 25-8* Status
Readout parameters informing about the operating status of the cascade controller and the pumps controlled.
25-80 Cascade Status
Range:
0 N/A*
[0 - 0 N/A]
Function:
This parameter is only active if the option selected in par. 25-50
from
Off
[0].
This parameter sets the time between stopping the old variable speed pump and starting another
pump as a new variable speed pump. Refer to par. 25-56
for description of staging and alternation.
Function:
This parameter is only active if the option selected in par. 25-50
Off
from
[0].
This parameter sets the time between stopping the old variable speed pump and starting this pump
as a new fixed speed pump. Refer to par. 25-56
description of staging and alternation.
Function:
Read out of the status of the Cascade Controller.
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Lead Pump Alternation
, is different
Staging Mode at Alternation
, the illustration
Lead Pump Alternation
, is different
Staging Mode at Alternation
, the illustration for
3
251