Motor Speed Unit; Regional Settings; Operating State At Power-Up; Local Mode Unit - Danfoss VLT Programming Manual

Hvac drive
Hide thumbs Also See for VLT:
Table of Contents

Advertisement

®
VLT
HVAC Drive Programming Guide
[51]
Bahasa Indonesia
[99]
Unknown

0-02 Motor Speed Unit

Option:
[0]
RPM
[1] *
Hz

0-03 Regional Settings

Option:
[0] *
International
[1]
North America
The setting not used is made invisible.

0-04 Operating State at Power-up

Option:
[0] *
Resume
[1]
Forced stop, ref=old

0-05 Local Mode Unit

Option:
[0] *
As Motor Speed Unit
[1]
%
Part of Language package 2
Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par. 0-02
Settings
. The default setting of par. 0-02
on which region of the world the frequency converter is supplied to, but can be re-programmed as
required.
NB!
Motor Speed Unit
Changing the
It is recommended to select the motor speed unit first, before modifying other
parameters.
Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in
terms of motor speed (RPM).
Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in
terms of output frequency to the motor (Hz).
Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par. 0-02
Settings
. The default setting of par. 0-02
on which region of the world the frequency converter is supplied to but can be re-programmed as
required.
Motor Power [kW]
Sets par. 1-20
units to [kW] and the default value of par. 1-23
cy
[50 Hz].
Sets par. 1-21
Motor Power [HP]
units to HP and the default value of par. 1-23
60 Hz.
Function:
Select the operating mode upon reconnection of the frequency converter to mains voltage after
power down when operating in Hand (local)mode.
Resumes operation of the frequency converter maintaining the same local reference and the same
start/stop condition (applied by [Hand On]/[Off] on the LCP or Hand Start via a digital input as
before the frequency converter was powered down.
Uses saved reference [1] to stop the frequency converter but at the same time retain in memory
the local speed reference prior to power down. After mains voltage is reconnected and after re-
ceiving a start command (using the LCP [Hand On] button or Hand Start command via a digital
input) the frequency converter restarts and operates at the retained speed reference.
Function:
Defines if the local reference unit should be displayed in terms of the motor shaft speed (in RPM/
Hz) or as percent.
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Motor Speed Unit
and par. 0-03
Motor Speed Unit
Regional Settings
and par. 0-03
will reset certain parameters to their initial value.
Motor Speed Unit
and par. 0-03
Motor Speed Unit
and par. 0-03
Regional Settings
Regional
3
depends
Regional
depends
Motor Frequen-
Motor Frequency
to
33