Commissioning and Diagnostics
Startup of the ET 200S
Switch on supply voltage
I/O device sets outputs to
to "0" and imports the
configured device name
(with connection to switch)
(without connection to switch)
I/O device receives
connect telegram and
from the I/O controller
data transfer possible.
Figure 6-35
Note
The IM151-3 PN interface module supports the default startup.
In this case the following conditions apply:
The default parameters are used (see the parameters for the electronic
•
modules).
All supply voltages must be switched on at the power modules.
•
6-60
for I/O device
from the MMC
"ON" LED lights
"BF" LED flashes
"BF" LED lights
startup data sets
Are the subscribed
modules present?
Yes
"BF" LED off;
inputs and outputs
are enabled;
Configuring the ET 200S on PROFINET IO
No
Remedy: Alignment of online
and offline configuration data
ET 200S Distributed I/O System
EWA-4NEB 780602402-12