Pulse - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

2Pulse

Table 6-20 2PULSE
Error type
1
00001: Short-circuit
D
9
01001: Error
D
16
10000: Parameter
D
assignment error
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Meaning
Short circuit of the sensor
supply or the actuator.
Internal module error occurred.
Parameters have not been
assigned to the module.
Commissioning and Diagnostics
Remedy
Check the wiring to the
momentary-contact switches
and the actuators. Correct the
process wiring.
Replace the module.
Adjust the parameter
assignment.
6-45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents