Power modules
Technical data
Dimensions and weight
Dimensions
W x H x D (mm)
Weight
Voltages, currents, electrical potentials
Rated load voltage
Overvoltage protection
Max. current capacity
for 24--56.7 VDC
for 24--48/120/230 VAC
Short-circuit protection
Electrical isolation
Between rated load
voltage and backplane
bus
Between the
power modules
Insulation tested with
Current consumption
From the backplane bus
From load voltage L1/L+
(without load)
Power loss of the module
10-14
15 x 81 x 52
34g
24--56.7 VDC
24--48 VAC/
120 V/230 VAC
Yes
1)
10A
to 30°C: max. 10A
(164 ft)
to 40°C: max. 9A
(164 ft)
to 60°C: max. 7A
(164 ft)
to 30°C: max. 8A
(164 ft)
to 40°C: max. 7A
(164 ft)
to 60°C: max. 5A
(164 ft)
yes, IEC 127-2/1,
250 V, 10 A,
fast-acting fuse
(5 x 20 mm),
1)
replaceable
Yes
Yes
1500 VAC
max. 9.5mA (164 ft)
max. 9mA (164 ft)
Max. 5W
Status, alarms, diagnostics
Diagnostics function
Group error
Rated load voltage
monitoring
Fuses
Reading of diagnostic
data
The fuses on this module are only auxiliary
fuses; external overcurrent protection (suitable
for branch circuits depending on the local
electrotechnical regulations) is required in the
power supply cables of the load current circuit.
ET 200S Distributed I/O System
Yes
red LED "SF"
Green LED "PWR"
Green LED "FSG"
Yes
EWA-4NEB 780602402-12