Power modules
Technical data
Dimensions and weight
Dimensions
W x H x D (mm)
Weight
Voltages, currents, electrical potentials
Rated load voltage
•
Overvoltage protection
Max. current capacity
•
for 24--56.7 VDC
•
for 24--48/120/230 VAC
•
Short-circuit protection
Electrical isolation
•
Between rated load
voltage and backplane
bus
•
Between the
power modules
Insulation tested with
Current consumption
From the backplane bus
•
From load voltage L1/L+
(without load)
Power loss of the module
10-14
15 x 81 x 52
34g
24--56.7 VDC
24--48 VAC/
120 V/230 VAC
Yes
1)
10A
to 30°C: max. 10A
(164 ft)
to 40°C: max. 9A
(164 ft)
to 60°C: max. 7A
(164 ft)
to 30°C: max. 8A
(164 ft)
to 40°C: max. 7A
(164 ft)
to 60°C: max. 5A
(164 ft)
yes, IEC 127-2/1,
250 V, 10 A,
fast-acting fuse
(5 x 20 mm),
1)
replaceable
Yes
Yes
1500 VAC
max. 9.5mA (164 ft)
max. 9mA (164 ft)
Max. 5W
Status, alarms, diagnostics
Diagnostics function
•
Group error
•
Rated load voltage
monitoring
•
Fuses
•
Reading of diagnostic
data
The fuses on this module are only auxiliary
fuses; external overcurrent protection (suitable
for branch circuits depending on the local
electrotechnical regulations) is required in the
power supply cables of the load current circuit.
ET 200S Distributed I/O System
Yes
red LED "SF"
Green LED "PWR"
Green LED "FSG"
Yes
EWA-4NEB 780602402-12