Operating The Et 200S On A Grounded Supply - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

24 VDC supply
The following table tells you what you have to do with regard to the 24 VDC supply.
Buildings
24 VDC supply lines,
signal lines
24 VDC supply
Protection against outside electrical influences
The following table tells you what to do to provide protection against electrical
influences or faults.
All plants or systems in
which the ET 200S is
integrated
Supply, signal, and bus
lines
Signal and bus lines
5.2

Operating the ET 200S on a grounded supply

In this section, you will find information on the overall setup of an ET 200S
distributed I/O system on a grounded supply (TN-S system). The specific subjects
discussed are:
• Circuit-breaking devices, short-circuit and overload protection in accordance
with DIN VDE 0100 and DIN VDE 0113
• Load power supplies and load circuits
Definition: Grounded mains
In a grounded supply, the neutral conductor of the system is grounded. A mere
ground fault between a live conductor and ground or a grounded section of the
plant causes the protective devices to trip.
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
With ...
Outdoor lightning
protection
Indoor lightning
protection
Safe (electrical) isolation of extra-low voltage
With ...
The plant or system is connected to a protective
conductor for diverting electromagnetic interference.
The wiring arrangement and installation are correct.
Any break of a line or conductor does not result in
undefined states of the plant or system.
Pay attention to ...
Take lightning protection
precautions
(for example, lightning
conductors)
You must ensure that...
Wiring and Fitting
5-3