Analog Electronic Modules
Analog Value Formation
Resolution (including sign)
Conversion time (per
channel)
Settling time
For resistive load
For capacitive load
For inductive load
Interference Suppression, Error Limits
Crosstalk between outputs
Operational error limits
(across the temperature
range, in relation to output
range)
Basic error limit
(operational error limit at
25 _C, related to the input
range)
Temperature error (in
relation to output range)
Linearity error (in relation
to output range)
Repetition accuracy
(in transient state at 25 _C,
relative to output range)
Output ripple (in relation to
output range, bandwidth 0
to 50 kHz)
12-114
20 mA/ 16 Bit
¦
4 to 20 mA/15 bits
Max. 1.0 ms
0.25 ms
1.0 ms
0.5 ms
> 60 dB
0.07 %
(at 250 Ω load
resistance)
0.3 %
(at all other load
resistances)
0.03 %
(at 250 Ω load
resistance)
0.26 %
(at all other load
resistances)
0.001 %/K
0.02 %
0.01 %
0.02 %
Data for selection of the actuator
Output range (nominal
value)
Load impedance (in the
nominal range of the
output)
For current outputs
For inductive load
Current output
No-load voltage
Destruction limit for
externally applied
voltages/currents
Voltage measured
between the outputs
and M
ANA
Current
Connection of actuators
Current output
2-wire connection
ET 200S Distributed I/O System
20 mA
4 to 20 mA
max. 500Ω
1 mH
18 V
Max. 15 V
continuous; 75 V for
max. 1 s (sampling
ratio 1:20)
max. DC 50 mA
possible
EWA-4NEB 780602402-12