Commissioning and Diagnostics
Power module error types
The diagnostic message is reported on channel 0 and applies to the whole module.
Table 6-12 Power module error types
Power modules electronic
modules
PM-E 24--48
PM-E 24
VDC/
VDC
120--230 VAC
PM-E
24--48 VDC
------
Digital electronic module error types
Table 6-13 Digital electronic module error types
Digital electronic
modules
2DI 24 VDC High
Feature
4DI 24 VDC High
Feature
6-40
Error type
17
10001: Encoder or
D
load voltage missing
18
10010: Fuse defect
D
Error type
1
00001: Short-circuit
D
1
00001: Short-circuit
D
(in connection with
IM151-1 BASIC /
IM151-1 STANDARD,
as of
6ES7 151-1AA02 0AB0,
IM151-1 FO
STANDARD, as of
6ES7 151-1AB01-0AB0)
or IM151-1 HIGH
FEATURE
26
11010: External
D
error/fault
(in connection with
IM151-1 STANDARD, to
6ES7 151-1AA01-0AB0
or IM151-1 FO
STANDARD, to
6ES7 151-1AB00-0AB0)
Meaning
No supply voltage,
or inadequate
supply voltage.
The fuse in the
power module has
tripped.
Meaning
Short circuit of the
sensor supply. The
diagnostic message
is issued on channel
0 and applies to the
whole module.
Short circuit of the
sensor supply. The
diagnostic message
is issued on channel
0 and applies to the
whole module.
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Remedy
Correct the process
wiring. Check the
supply voltage.
Replace the fuse.
Remedy
Correct the process
wiring (sensor
wiring).
Correct the process
wiring (sensor
wiring).