Configuration table in your configuration software and address space
The byte addresses of the inputs and outputs can be freely selected (if the
configuration software supports this). The bit addresses result automatically from
the sequence of the grouped modules.
Table 6-2
Configuration table and address space
Slot
1
6ES7 138-4CA00-0AA0 PM-E 24 VDC
2
6ES7 131-4BB00-0AB0 2DI 24 VDC
3
6ES7 131-4BB00-0AB0*2DI 24 VDC
4
6ES7 134-4FB00-0AB0 2AI U
5
6ES7 135-4GB00-0AB0 2AO I
6
6ES7 131-4BD00-0AA0*4DI 24 VDC
7
6ES7 132-4BD00-0AA0 4DO 24 VDC
8
6ES7 132-4BB00-0AB0*2DO 24 VDC
9
6ES7 132-4HB00-0AB0*2DO Rel.
10
6ES7 134-4FB00-0AB0 2AI U
11
6ES7 135-4GB00-0AB0 2AO I
12
6ES7 138-4CA00-0AA0 PM-E 24 VDC
13
6ES7 132-4BB30-0AB0 2DO 24 VDC
14
6ES7 132-4BB30-0AB0* 2DO 24 VDC
15
6ES7 138-4CA00-0AA0 PM-E 230 VAC
16
6ES7 132-4FB00-0AB0* 2DO 230 V
17
6ES7 132-4FB00-0AB0* 2DO 230 V
18
3RK1903-0BA00 PM-D
19
3RK1301-xxB00-0AA0 DS
20
3RK1301-xxB00-0AA0 *DS
21
3RK1301-xxB00-0AA0 DS
No grouping
If you do not want to group the configuration of the ET 200S distributed I/O system
digital input/output modules and motor starters in a single byte, use only those
module designations without "*" in the hardware catalog of your configuration
software.
Each electronic module/motor starter will then occupy one byte in the input or
output area of the process image.
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Module
Commissioning and Diagnostics
Grouping
I/O address
Inputs
------
------
Yes
0.0 to 0.1
0.2 to 0.3
No
1 to 4
No
Yes
0.4 to 0.7
Yes
No
5 to 8
No
------
------
Yes
Yes
------
------
Yes
Yes
------
------
Yes
9.0 to 9.3
9.4 to 9.7
Yes
10.0 to 10.3
Outputs
------
0 to 3
4.0 to 4.3
4.4 to 4.5
4.6 to 4.7
5 to 8
------
9.0 to 9.1
9.2 to 9.3
------
9.4 to 9.5
9.6 to 9.7
------
10.0 to 10.3
10.4 to 10.7
11.0 to 11.3
6-9