Configuration Options
The identification data are assigned to the indices as per Table 3-14.
The data structures in data sets 231 to 234 correspond to the specifications of the
PROFIBUS Guideline -- Order No. 3.502, Version 1.1, May 2003.
Table 3-14 Identification data

Identification data

Identification data 0: Index 1 (data record 231)
MANUFACTURER_ID
ORDER_ID
SERIAL_NUMBER
HARDWARE_REVISION
SOFTWARE_REVISION
REVISION_COUNTER
PROFILE_ID
PROFILE_SPECIFIC_
TYPE
IM_VERSION
IM_SUPPORTED
Maintenance data 1: Index 2 (data record 232)
TAG_FUNCTION
TAG_LOCATION
Maintenance data 2: Index 3 (data record 233)
INSTALLATION_DATE
RESERVED
Maintenance data 3: Index 4 (data record 234)
DESCRIPTOR
3-44
Access
Default setting
read (2 bytes)
2A hex (=42 dec)
read (20 bytes)
depends on the
module
read (16 bytes)
irrelevant
read (2 bytes)
irrelevant
read (4 bytes)
Firmware version
read (2 bytes)
--
read (2 bytes)
F600 hex
read (2 bytes)
0005 hex
read (2 bytes)
0101 hex
read (2 bytes)
000E hex
read / write (32
--
bytes)
read / write (22
--
bytes)
read / write (16
--
bytes)
read / write (38
--
bytes)
read / write (54
--
bytes)
Explanation
The name of the manufacturer is
stored here. (42 dec = SIEMENS
AG)
Order number of the module
This indicates the firmware
version of the module.
Provides information on the
parameter
changes on the module. REVISION_
COUNTER increments with each
change.
Generic Device
on interface modules
Shows the version of the
identification data
(0101 hex = Version 1.1)
Provides information on available
identification data (index 2 to 4)
Enter a unique tag for the module
here.
Enter the installation location of the
module here.
Enter the installation date of the
module here.
Reserved
Enter a comment describing the
module here.
ET 200S Distributed I/O System