Commissioning

8.1

PROFINET IO

8.1.1

Commissioning ET 200AL on PROFINET IO

Introduction
The commissioning of your distributed I/O system depends on the system configuration. The
following procedure describes the commissioning of the ET 200AL distributed I/O system on
an IO controller.
Requirements for the ET 200AL distributed I/O system on the PROFINET IO
Note
Performing tests
You must ensure the safety of your plant. You therefore need to perform a complete
functional test and the necessary safety checks before the final commissioning of a plant.
Also plan the tests to include any possible foreseeable errors. This will allow you to prevent
people or plants from being placed in danger during operation.
Procedure
The following table shows the chapters/documents in which the required actions are
described.
Table 8- 1
Step
1
2
3
4
5
Reference
You can find additional information on assigning the PROFINET IO parameters in the
PROFINET with STEP 7 V14
(https://support.industry.siemens.com/cs/ww/en/view/49948856) function manual.
Distributed I/O system
System Manual, 08/2019, A5E31861578-AG
Requirements for the ET 200AL distributed I/O system on the PROFINET IO
Procedure
Mounting the ET 200AL interface module
Wiring the ET 200AL interface module
Configuring the ET 200AL interface module
Turning on the supply voltage for the ET 200AL
interface module
ET 200AL interface module automatically
switches to RUN mode
See...
Section Mounting (Page 20)
Section Connecting (Page 25)
Section Configuring (Page 44)
IM 157-1 PN interface module
(https://support.industry.siemens.com/cs/w
w/en/view/89254863) manual
-
8
65