Interrupts, for example, removing and inserting the 2 DI 24 VDC High Feature
digital electronic module
1. Remove the 2 DI 24 VDC High Feature electronic module (e.g. from slot 2)
from the terminal module during operation.
2. Watch the status LEDs on the IM 151-3 PN:
-- SF: lit ⇒ diagnostic message exists.
-- BF: Off
-- ON: lit
Result: The ET 200S continues to operate problem-free.
3. OB 83 is started in the event of a remove interrupt. In OB 83 start SFB 52.
Evaluate the diagnostic data set E002
Byte
Header information
0 and 1
2 and 3
4 and 5
6 and 7
IO device header information
8 and 9
10 and 11
12 and 13
Configuration data of slots
14 and 15
16 to 19
20 and 21
22 and 23
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Contents
8104
Data record with discrepancies between the expected and
H
actual configuration
0014
20 bytes follow
H
0100
Version 1.0
H
0001
0001
if the preset deviates from the actual configuration
H
H
0000
Fixed
H
0000
Fixed
H
0001
Number of slots in which there is a discrepancy between the
H
expected and actual configuration
0002
Slot number of the slot with a discrepancy between
H
expected and actual configuration
XXXXXXXX
Identification of the inserted module
H
0000
No module inserted
H
0000
Number of submodule slots with preset/actual deviation
H
Because the content is 0000
submodule data.
Brief Instructions on Commissioning ET 200S
.
H
Meaning
, there are no additional
H
2-17